Furnace tune-up, Lakewood
- Equipment
- Gas furnace, 2011, 80,000 BTU/h input on the plate
- Altitude setup
- High-altitude orifices, checked against the manufacturer's chart
- Manifold gas pressure
- 3.2 in. w.c.
- Temperature rise
- 48°F, plate range 35 to 65°F
- CO in the flue, air-free
- 22 ppm
- CO in the living room
- 0 ppm
- Flame sensor current
- 4.6 µA after cleaning
- Heat exchanger
- Camera inspection, no cracks found
- Filter
- 16 × 25 × 1 in., replaced
Good for this winter. The inducer motor hums for a few seconds at start-up. We'll listen to it again at the spring visit.